Can Online Identification Replace a Floor-Plan Prior? Field Testing a New HVAC Control Method

Can Online Identification Replace a Floor-Plan Prior? Field Testing a New HVAC Control Method

Research shows online identification can replace a floor-plan prior, letting HVAC control run in unknown buildings without historical data.

The study addresses the challenge of deploying HVAC control strategies in unfamiliar buildings by proposing an adaptive method that uses only building metadata and sensor streams. A first-order grey-box model is initialized from the floor plan and updated online via recursive least squares. In custom simulations, it significantly outperformed the PID baseline (0.145x and 0.159x) and two ASHRAE Guideline 36 implementations. Ablation shows either online identification or the floor-plan prior alone recovers most performance, while missing both costs 20%-42%. However, results were not fully reproduced on BOPTEST, where the floor-plan-only variant was most unstable, indicating prior effectiveness depends on the environment and requires validation before deployment.

In the field of smart buildings, getting an HVAC control strategy to run directly in an office building it has never seen before has long been a challenge. A recent study proposed an adaptive control method that does not rely on operational data from the target building, and validated through simulation experiments the relationship between online identification and a floor-plan prior. The research stems from The Smart Buildings Challenge, which requires controllers to perform control tasks in unfamiliar buildings using only building metadata and sensor streams.

rss source: Online Identification Can Replace a Floor-Plan Prior on Unseen Buildings

Controller Design: From Grey-Box Model to Online Updates

The controller designed by the research team does not access any data from the target building before operation, nor is it tuned separately for each building; the only global constants are set in development scenarios. Each zone uses a first-order grey-box model, with initial model coefficients computed from the floor plan and subsequently updated online via recursive least squares. The model outputs are then transformed into actual device commands through a planner and closed-form mapping.

The core idea is to use the floor plan to provide an initial "prior" and then use online identification to correct the model based on real-time data. This leverages prior knowledge while retaining adaptability.

Grey-box models are a class of modeling methods between white-box (fully based on physical mechanisms) and black-box (purely data-driven): they retain a known physical structure (such as the form of a first-order heat balance equation) but allow some parameters to be unknown and estimated from data. In this study, the first-order grey-box model for each zone can be understood as describing zone temperature dynamics as a function of thermal capacitance, thermal resistance, and internal/external disturbances, where coefficients such as thermal capacitance are initially estimated from the floor plan and then corrected via online data. Compared to pure black-box models, grey-box models require less data and have stronger extrapolation capability, making them suitable as a starting point when operational data from the target building is lacking.

Recursive least squares (RLS) is an online parameter estimation algorithm that recursively updates parameter estimates as new data arrives, without reprocessing all historical data. Its standard form is: for each new sample, first compute the prediction error, then correct the parameters according to a gain vector, with the gain decaying as the covariance matrix updates. RLS has low computational cost and fast convergence and is commonly used in adaptive control and system identification. In this study, the controller uses RLS to continuously correct the grey-box model coefficients, allowing the model to gradually approach the true dynamics as the building operates, thereby supporting the subsequent planner in generating device commands.

Performance Comparison with Baselines and the ASHRAE Standard

On two sets of building and weather data generated by the team (a validation set and a stress set containing real-year weather), the controller scored 0.145 times and 0.159 times the startup kit PID baseline, respectively, and scored 0.095 times on a holdout set evaluated once after the final fixed version. In other words, performance is significantly better than the traditional baseline.

Compared with two implementations of ASHRAE Guideline 36, the controller also showed advantages: on each data set, its score was 0.60 to 0.71 times that of the basic version, and 0.83 to 0.96 times that of a version partially tuned on the public leaderboard. The latter won one scenario out of 54. However, when the frost target for unoccupied zones was set to 5°C, the gap with the tuned version narrowed to 1.4% on the stress set, with one of the six buildings differing by 0.2%.

ASHRAE Guideline 36 is a guideline published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers for high-performance HVAC control sequences, aimed at improving energy efficiency and indoor environmental quality through standardized, optimized control logic (such as VAV box pressure control, zone temperature reset, ventilation optimization, etc.). It is generally regarded as an advanced industry baseline rather than simple PID control. This article uses it as a comparison because the guideline represents a relatively mature high-performance control strategy in engineering practice. The study implemented its basic version and a version tuned on the public leaderboard to measure the actual gain of the adaptive controller relative to industry standards. It should be noted that the control sequences in the guideline still depend on building-specific setpoints and configurations, whereas the method in this paper emphasizes deployment without operational data from the target building; the two differ in their prerequisites.

Ablation Experiments: Contributions of the Prior and Online Identification

The research team conducted ablation experiments on a reduced-order model, removing the floor-plan prior and online identification separately. Results showed that on the validation set, stress set, and holdout set, the cost of removing both simultaneously was 28%, 20%, and 42%, respectively, far greater than the sum of the two effects acting individually. In other words, as long as either building-specific information source is retained, most of the performance lost when both are missing can be recovered.

This finding supports the claim in the paper's title: online identification can replace a floor-plan prior. But the prerequisite is that at least one of the two is retained; if both are removed, performance drops sharply.

Ablation experiments originate from experimental psychology and machine learning and refer to systematically removing a component or information source of a model and observing performance changes to quantify the importance of that component. In this study, the ablation targets are the two mechanisms of floor-plan prior and online identification. By removing each separately, removing both simultaneously, and comparing performance losses, one can determine whether the two are redundant, complementary, or synergistic. The statement in the paper that "the cost of removing both simultaneously is far greater than the sum of the two effects acting individually" implies subadditivity: when either information source exists alone, it already covers most requirements, so the marginal loss of missing the other is small; but when both are missing, the controller has neither initial structure nor adaptive correction, and performance drops sharply. This analysis helps clarify the conditions under which the method holds.

Cross-Simulator Validation: Results Are Not Fully Consistent

On a single-story office building in a second simulator, BOPTEST, the conclusions were not fully reproduced: with online identification enabled, the two priors (the floor-plan prior and another prior) produced similar results; but when only the floor-plan prior was used and the constants were fitted on the competition simulator, this scheme became the most unstable branch. This suggests that the effectiveness of the prior may depend on the simulator environment, and caution is needed when crossing platforms.

BOPTEST (Building Optimization Performance Test) is a building control benchmarking platform developed under the International Energy Agency (IEA) EBC Annex 60/81 framework, providing multiple standardized building models, weather data, and test scenarios for fair comparison of different control algorithms. Compared with the competition's custom simulator, BOPTEST may differ in model structure, time step, sensor noise, and boundary conditions, so the same controller may perform differently on different platforms. The inconsistent reproduction experiments on the BOPTEST single-story office building in this paper suggest that control strategies are sensitive to the simulator environment, and when transferring across platforms, the validity of prior assumptions and parameter fitting needs to be re-validated.

Insights and Limitations

Overall, these simulation results support testing adaptive control initialized from floor plans in buildings that have "drawings but no operational data." The value of this method lies in reducing dependence on historical data from the target building while online identification provides adaptability. However, the inconsistent results on BOPTEST also remind us that the role of the prior is not universal, and validation in the target environment is needed before actual deployment.

Future work can further explore the convergence speed of online identification, robustness to sensor noise, and performance in more real buildings.

One-line Summary

Research demonstrates that online identification can replace a floor-plan prior, enabling HVAC control to operate in unknown buildings without historical data.

Paragraph Summary

Aiming at the problem that HVAC control strategies in smart buildings are difficult to deploy directly in unfamiliar buildings, this study proposes an adaptive control method that relies only on building metadata and sensor streams. The controller uses a first-order grey-box model, computes initial coefficients from the floor plan, and updates online via recursive least squares. In the team's own simulation, its score was significantly better than the PID baseline (0.145 times and 0.159 times) and also better than two implementations of ASHRAE Guideline 36. Ablation experiments show that either online identification or the floor-plan prior alone can recover most performance, while missing both costs 20%-42%. However, results were not fully reproduced on the BOPTEST simulator; the scheme using only the floor-plan prior was the most unstable, suggesting that prior effectiveness depends on the environment and must be validated before actual deployment.

#HVAC control#online identification#floor plan prior#ASHRAE Guideline 36#BOPTEST#grey-box model#recursive least squares#smart buildings